Enhancing Fire Safety Performance of Flexible Fire-Resistant Cables: A Comprehensive Review and Analysis

 

Temperature change inside core of YTTW cable

Introduction

As power systems continue to evolve, the demand for high fire-resistant cables has increased significantly. Fire-resistant cables play a crucial role in ensuring the safety of electrical installations, especially in densely populated buildings. This article reviews the research on the fire safety performance of flexible fire-resistant cables, comparing testing standards, fire resistance characteristics, and offering insights into improving cable design for enhanced safety.


Overview of Fire-Resistant Cables

Fire-resistant cables are categorized based on their insulation and sheathing materials. The most common types include:

  • Rigid fire-resistant cables (BTTZ): Utilize magnesium oxide insulation, offering excellent fire resistance but high installation costs.

  • Flexible fire-resistant cables (BBTRZ, BTLY, YTTW, RTTZ): Insulated with mica tape and further protected by non-metallic or metallic sheaths.

Cable TypeInsulationSheathVoltage RatingStandard
N-YJVMica tapeNon-metallic0.6/1 kVGB/T 19666-2019
BBTRZMica tapeNon-metallic0.6/1 kVQ/GZNY 11-2020
BTLYMica tapeAluminum + non-metallic0.6/1 kVT/GDWCA 0062-2020
YTTWMica tapeCopper0.6/1 kVJG/T 313-2014
RTTZMica tapeCopper450/750V & 0.6/1 kVGB/T 34926-2017
BTTZMagnesium oxideCopper750VGB/T 13033.1-2007

Each cable type follows specific fire resistance testing standards, impacting its performance in real-world applications.


Fire Resistance Testing Methods

Fire resistance testing evaluates a cable’s ability to withstand extreme conditions while maintaining electrical integrity. Major testing methods include:

StandardTest TypeApplicable VoltageTemperature (°C)Duration (min)Additional Factors
GB/T 19666-2019Pure fire exposure≤1 kV75090None
Fire + mechanical impact≤1 kV830120Mechanical shocks
Fire + mechanical impact + water spray≤1 kV830120Water spray in last 15 min
BS 6387:2013Fire only≤1 kV, Ø ≤20mm950180None
Fire + water≤1 kV, Ø ≤20mm6503015 min fire, 15 min fire + water
Fire + impact≤1 kV, Ø ≤20mm95015Mechanical impact
BS 8491:2008Fire + mechanical impact + water spray≤1 kV, Ø >20mm830-870120Final 5 min with water spray

The differences in testing standards can lead to inconsistencies in cable selection for fire-critical applications.


Key Findings from Fire Performance Tests

1. Internal Temperature Changes

Experiments on YTTW cables (4×2.5 mm² and 3×35 mm²) under 950-1000°C revealed that:

  • Small-section cables experience rapid temperature rises, reaching 700°C within 8 minutes, increasing brittleness.

  • Large-section cables maintain a lower, more stable temperature (~650°C).

Implication: Insulating materials must maintain integrity at temperatures up to 800°C.

2. Insulation Resistance Under High Temperatures

Mica tape and ceramic silicone were tested for electrical insulation:

Temperature (°C)Mica Tape (Ω)Ceramic Silicone (Ω)
1502.2×10¹²3.3×10⁷
4003.8×10⁹2.5×10⁷
6001.4×10⁸1.5×10⁵
8007273.6×10³
90021183

Implication: Mica tape experiences insulation failure between 700-800°C, requiring additional protective layers.

3. Internal Pressure During Fire Exposure

High-temperature exposure (950-1000°C) on 1.5m and 100m YTTW cables showed:

  • Shorter cables had increased internal pressure (0.50 MPa), leading to sheath rupture at 9.5 minutes.

  • Longer cables maintained stable internal pressure.

Implication: Pressure management must be considered in flexible fire-resistant cable designs.

4. Conductor Temperature Rise

Tests on different cable types at 706A revealed significant variation in heat dissipation:

Cable TypeMaximum Conductor Temperature (°C)
N-YJV91.4
BBTRZ71.7
BTLY62.7
YTTW131.7
RTTZ131.7

Implication: Different structures and materials impact heat dissipation, affecting the actual current-carrying capacity.

5. Sheath Surface Temperature

The external surface temperature after full-load operation for 1 hour was:

Cable TypeSurface Temperature (°C)
N-YJV58
BBTRZ73
BTLY78
YTTW69
RTTZ69

Implication: High sheath temperatures pose risks of burns and require additional insulation or separation measures.


Recommendations for Improving Fire-Resistant Cables

Based on experimental findings, several design improvements are suggested:

  1. Enhance Insulation Material: Improve mica tape and ceramic silicone insulation to withstand temperatures beyond 800°C.

  2. Optimize Protective Layers: Introduce thermal barriers to reduce temperature spikes in cable cores.

  3. Improve Pressure Venting: Ensure long cables have ventilation pathways to prevent pressure buildup.

  4. Increase Heat Dissipation: Use materials with better thermal conductivity to enhance cooling efficiency.

  5. Implement Standardized Testing: Adopt stricter international standards (e.g., BS 8491:2008) for consistent product performance.


Conclusion

The fire safety performance of flexible fire-resistant cables is influenced by insulation integrity, conductor heating, and internal pressure variations. Future developments should focus on enhancing insulation materials and improving testing methodologies. Ensuring consistency across different standards will be key to increasing safety in high-risk electrical installations.

By addressing these factors, manufacturers can produce more reliable fire-resistant cables, helping to prevent electrical failures in fire-prone environments.


Keywords

Flexible fire-resistant cables, fire safety, insulation resistance, temperature stability, fire resistance testing.

References

  1. Xiong, X., Peng, L., Qiu, X. (2024). Research on Fire Safety Performance of Flexible Fire-Resistant CablesWire & Cable, No. 5, 2024.

  2. GB/T 19666-2019: General Rules for Flame Retardant and Fire-Resistant Cables.

  3. BS 6387:2013: Performance Requirements for Fire-Resistant Electrical Cables.

  4. BS 8491:2008: Fire Resistance Tests for Large Diameter Cables.  Source: JianYunCable

Comments

Popular posts from this blog

Understanding Voltage Levels and Cable Types in China's Power Industry

Comparison of Flame Retardant Standards for Electric Wires and Cables

What Are Trailing Cables and Where Are They Used?

Understanding Low Voltage Power Cables: A Comprehensive Guide

Medium Voltage Cable Life Expectancy: Factors and Insights

4 AWG Wire: Definition, Specifications, Ampacity, and MM² Equivalent

Optimized Design of Smooth Aluminum Sheath Thickness for High-Voltage Cables Using the Short-Circuit Capacity Method

0.6/1kV CU/XLPE/PVC Cable

Understanding LSOH Cables: Safety and Applications

Understanding Voltage Levels and Cable Types in China's Power Industry

All Cable Products-Henan Province Jianyun Cable Co., Ltd.